Product Specification
Place of Origin: China
Brand Name: Purple Horn
Model Number: KCR153
Minimum Order Quantity: 10 pcs
Price: negotiable
Standard Packaging: Each unit packed in a individual box
Delivery Time: 20 days and depends on ordering quantity
Payment Terms: T/T, L/C
Supply Ability: 10000 pcs per month

Product Summary

AC IDMT Automatic Overcurrent Protection Relay 5A Single Phase A relay is intended protect loads or circuits from excessive current. Description: Purple Horn overcurrent protection delivers comprehensive protection schemes for low voltage applications. All Mikro's overcurrent units are microprocesso...

Product Details

Highlight:

Overcurrent Protection Relay

,

Power System Protection Relays

Color: White
Current Rating: 5A
Frequency: 50/60Hz
Contact: Silver Ally
Relay: IDMT
Installation: Panel,DIN Rail , Screws

Product Description

 

AC IDMT Automatic Overcurrent Protection Relay 5A Single Phase

 

 

A relay  is intended protect loads or circuits from excessive current.

 

 

Description:

 

Purple Horn overcurrent protection delivers comprehensive protection schemes for low voltage applications. All Mikro's overcurrent units are microprocessor-based numerical relays and are housed in high-strength protective casing. The models in the range provide a wealth of options including programmable relay outputs to static, and digital display or dial activated..

 

 

FEATURES 


A. Low-set inverse definite minimum time relay 
B. High-set instantaneous 
C. Separate low-set and high-set trip indicators 
D. Trip starting indication 

 

 

Specifications:

 

Settings

Current rating 

5A

Rated frequency

50/60Hz

Load

 < 0.3VA at In

Thermal withstand

4*ln

Auxiliary supply

Voltage

 198-265VAC

Frequency

 50/60Hz

 

 

SETTING RANGES 
Low-set: 2A to 6A; 40% to 120% 
Time multiplier: 0.01 to 1.0 
IDMT curve: Normal inverse 
High-set(l>>): i> to 5× l> 

 

 

CONTACTS 
Trip contact: Automatic reset type 
Contact rating: NC NO contact type 
                        6A. 250V AC 
                        Silver alloy contact material 
                        100, 000 electrical operations at rated currents 

 

 

IINDICATORS 
Trip indicator: Manual reset type 

 

 

PERFORMANCE 
Adjustable accuracy: Less than ± 5% 
Repeatability: Less than 0.5% of full scale

 

 

Benefit:

  • Accurate, reliable and more resistant to vibration and shock than traditional electromechanical relays
  • Current measurement based on fundamental frequency, prevents nuisance tripping
  • Digital display or dial activated for ease of use
  • Robust casing protects the unit from external interference
  • Complies with IEC 60255-26 standards

 

Applications:

 

Feeder incoming protection
Outgoing protection
Busbar protection

 

 

Full series: earth leakage relay, earth fault relay, overcurrent relay, zero phase transformer

 

 