Home ProductsAC Contactor

Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed

Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed

    • Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed
    • Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed
  • Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed

    Product Details:

    Place of Origin: China
    Brand Name: KRIPAL
    Certification: CE, UL
    Model Number: UKC1-22

    Payment & Shipping Terms:

    Minimum Order Quantity: 500pcs
    Price: negotiable
    Packaging Details: Each unit packed in a individual box
    Delivery Time: 20 days and depends on ordering quantity
    Payment Terms: T/T, L/C
    Supply Ability: 50000 pcs per month
    Contact Now
    Detailed Product Description
    Brand: KRIPAL Current Range: 9A 12A 18A 22A
    Poles: 3P Auxiliary: 1NO+1NC
    Contacts: Silver Coil: AC
    High Light:

    ac magnetic contactor

    ,

    definite purpose contactor

     

    Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed

     

     

    A Ccontactor is an electrically controlled switch used for switching a power circuit, similar to a relay  except with higher current ratings, which is controlled by a circuit which has a much lower power level than the switched circuit. 

     

    Description:

     

    UKC1 series AC Contactor is suitable for using in the circuits up to the rated voltage 660V AC50Hz or 60Hz,

     rated current up to 630A, for making, breaking, frequently starting & controlling the AC motor. Combined with

     the auxiliary contact block, timer delay & machine interlocking  device  etc,  it  becomes  the delay  contactor,  mechanical interlocking contactor, star-delta starter. 

     

    With the thermal overload relay, it is combined into the electromagnetic starter. The product conforms to 

    IEC60947-4-1 standard.

     

     

    Characteristics

     

    1. The cover for preventing electrical shock on the top of ac contactor and thermal overload relay

     

    2. The ac contactor and relay are classified into 3 frame sizes according to the external dimensions

     

    3. AC Contactor and relay can be connected directly without other fittings

     

    4. Installed by screws or on the 35mm DIN rail directly

     

     

    Specifications:

     
    Model UKC1-9 UKC1-12 UKC1-18 UKC1-22
    AC coil UKC1-9 UKC1-12 UKC1-18 UKC1-22
    DC coil UKD1-9 UKD1-12 UKD1-18 UKD1-22
    IEC-60947 AC1 Load 25A 25A 40A 40A
    AC3 Load 200~240V 2.5KW 11A 3.5KW13A 4.5KW18A 5.5KW 22A
    380~440V 4KW 9A 5.5KW12A 7.5KW18A 11KW 22A
    500~550V 4KW 7A 7.5KW12A 7.5KW13A 15KW 22A
    690V 4KW 5A 7.5KW 9A 7.5KW 9A 15KW 18A
    UL508 Current (Ith) 20A 25A 30A 32A
    Single phase 115V 0.5HP 0.5HP 1HP 2HP
    230V 1Hp 2Hp 3Hp 3Hp
    Three phase 200V 2HP 3HP 5HP 7.5HP
    230V 2HP 3HP 5HP 7.5HP
    460V 5HP 7.5HP 10HP 10HP
    575V 7.5HP 10HP 15HP 15HP
     

     

     

    Coil voltage(AC) :

    50Hz: 24V, 42V, 48V, 100V, 110V, 220V, 240V, 380V, 400V, 415V, 440V, 500V, 550V 
    60Hz: 24V, 48V, 110V, 120V, 208V, 220V, 240V, 277V, 380V, 440V, 480V, 600V 

     


    Coil voltage(DC): 

    12V, 20V, 24V, 48V, 60V, 80V, 100V, 110V, 125V, 200V, 220V, 250V 

     

     

    Installation & Connection: 


    Installation: Fixed by 35mm guide rail or screw (M4) 
    Connection: Main contact: Screw(M4)crimping terminal; Wire diameter: 2-14mm2 
    Auxiliary contact: Screw(M3.5)crimping terminal

     

     

    Characteristics:

     

    Electrical Motor Protection 3 Pole AC Contactor Definite Purpose with UL listed 0

    Contact Details
    Zhejiang KRIPAL Electric Co., Ltd.

    Contact Person: Allen

    Tel: +8613780109789

    Send your inquiry directly to us
    Best Products
    Other Products