Home ProductsAC Contactor

Waterproof Shockproof AC Contactor Magnetic Starter 240V.5.5KW 18-26A 220V. 50/60Hz OEM

Waterproof Shockproof AC Contactor Magnetic Starter 240V.5.5KW 18-26A 220V. 50/60Hz OEM

    • Waterproof Shockproof AC Contactor Magnetic Starter 240V.5.5KW 18-26A 220V. 50/60Hz OEM
    • Waterproof Shockproof AC Contactor Magnetic Starter 240V.5.5KW 18-26A 220V. 50/60Hz OEM
  • Waterproof Shockproof AC Contactor Magnetic Starter 240V.5.5KW 18-26A 220V. 50/60Hz OEM

    Product Details:

    Place of Origin: China
    Brand Name: KRIPAL
    Certification: CE
    Model Number: UKQ series

    Payment & Shipping Terms:

    Minimum Order Quantity: 500pcs
    Price: negotiable
    Packaging Details: Each unit packed in a individual box
    Delivery Time: 20 days and depends on ordering quantity
    Payment Terms: T/T, L/C
    Supply Ability: 50000 pcs per month
    Contact Now
    Detailed Product Description
    Current Range: 9,12,18,22,32,40,50,65,75,85A Current Range: 9,12,18,22,32,40,50,65,75,85A
    Auxiliary: 1NO+1NC Auxiliary: 1NO+1NC
    Auxiliary: 1NO+1NC Auxiliary: 1NO+1NC
    Auxiliary: 1NO+1NC Auxiliary: 1NO+1NC
    Contacts: 85% Silver Ag Contacts: 85% Silver Ag
    Coil: AC Coil: AC
    Coil: AC Coil: AC
    High Light:

    heat pump contactor

    ,

    ac magnetic contactor

    Waterproof shockproof AC Contactor Magnetic Starter 240V.5.5KW 18-26A 220V. 50/60Hz OEM acceptable

     

     

    Description:

     

    AC motor starters has a contactor and an overload relay, which will open the control voltage to the starter coil if it detects an overload on a motor. Overload relays may rely on heat produced by the motor current to operate a bimetal contact or release a contact held closed by a low-melting-point alloy.

    The overload relay opens a set of contacts that are wired in series with the supply to the contactor feeding the motor. The characteristics of the heaters can be matched to the motor so that the motor is protected against overload. Recently, microprocessor-controlled motor digital protective relays offer more comprehensive protection of motors.

     

    Waterproof shockproof AC Contactor Magnetic Starter 240V.5.5KW 18-26A 220V. 50/60Hz OEM acceptable

     

    Specifications:

     
    Model Rated ultimate(KW) Rated current(A) AC1 Type
    Single-phase motor Three-phase motor AC3 Type Three-phase motor AC3 Type
    110V 220V  200-220V 380V-440V 500V-550V 200-220V 380V-440V 500V-550V A
    UKQ-9MB 0.4 0.8 2.5 4 4 11 9 7 25
    UKQ-12MB 0.5 1 3.5 5.5 7.5 13 12 12 25
    UKQ-18MB 0.75 1.5 4.5 7.5 7.5 18 18 13 40
    UKQ-22MB 0.9 1.8 5.5 11 15 22 22 22 40
    UKQ-32MB 1.2 - 7.5 15 18.5 32 32 28 50
    UKQ-40MB 1.7 - 11 18.5 22 40 40 32 60
    UKQ-50B - - 15 22 30 50 50 43 80
    UKQ-65B - - 18.5 30 33 65 65 60 100
    UKQ-75B - - 22 37 37 75 75 64 110
    UKQ-85B - - 25 45 45 85 80 75 135

     

     

    Operation:

     

    Typically starters are operated by two push switches, a "start" switch which is normally-off (i.e. push-to-make) and a "stop" switch which is normally-on (i.e. push-to-break).

    When the motor is not running, although line voltage is available, no current is drawn by the starter or motor.

    When the "start" button is pressed, the motor is not powered directly, rather the electromagnet in the contactor is energized. The magnetic switch in the contactor then engages, simultaneously switching current to the motor and providing self-sustaining current to maintain its own state. Thus when the start button is released, the magnetic switch remains engaged and the motor remains running.

    Pressing the "stop" button breaks the circuit to the contactor which consequently de-energizes its electromagnet thus cutting current to the motor.

     

     

    Applications:

     

    AC motor starters are commonly found on equipment drawing several horsepower or higher. Examples include woodworking machinery such as cabinet saws or shapers. Machines with smaller loads, such as a drill press or most handheld tools normally use only a switch instead. Magnetic starters are stock components for many machines, and aftermarket starters are also available for use as replacements or for retrofitting older machines.

     

     

    Shockproof  inner package design:

     

     

    This foam design can protect the starter from damage during the shipment, this is designed by KRIPAL.

    Waterproof Shockproof AC Contactor Magnetic Starter 240V.5.5KW 18-26A 220V. 50/60Hz OEM 0

     

     

     

     

    Dimension:

     

    Waterproof Shockproof AC Contactor Magnetic Starter 240V.5.5KW 18-26A 220V. 50/60Hz OEM 1

     

     

     

     

     

     

    Contact Details
    Zhejiang KRIPAL Electric Co., Ltd.

    Contact Person: Allen

    Tel: +8613780109789

    Send your inquiry directly to us
    Best Products
    Other Products