Send Message
Home ProductsMini Circuit Breaker

3 Pole 10000A Earth Leakage Mini Circuit Breaker Overload Protection

3 Pole 10000A Earth Leakage Mini Circuit Breaker Overload Protection

  • 3 Pole 10000A Earth Leakage Mini Circuit Breaker Overload Protection
3 Pole 10000A Earth Leakage Mini Circuit Breaker Overload Protection
Product Details:
Place of Origin: China
Brand Name: KRIPAL
Certification: CE
Model Number: UKB7LE
Payment & Shipping Terms:
Minimum Order Quantity: 1000 pcs
Price: negotiable
Packaging Details: 12 poles packed in one small box and then in carton
Delivery Time: 20 days and depends on ordering quantity
Payment Terms: T/T, L/C
Supply Ability: 200000 pcs per month
Contact Now
Detailed Product Description
Breaking Capacity: 10 KA Poles Available: 1P, 2P, 3P, 3P+N, 4P
Ampere: 6A,10A,16A,20A,25A,32A,40A,50A,63A Residual Protection: Yes
Overload Protection: Yes Type: Mini Circuit Breaker
High Light:

compact circuit breaker

,

micro circuit breaker

 

3 Pole 10000A Earth Leakage Mini Circuit Breaker Overload Protection

 

 

The ELCB is applied to the circuit of AC 50Hz with rated voltage up to 400V, rated current up to 50A, power supply neutral point earthing. It's mainly used to protect person from getting an electric shock and protect the building′s circuit devices from over current, it also can protect the earthing fault.

The ELCB is according with IEC61009-1:1991, GB16917.1-1997 standard.

 

 

Specifications:

 
Technology Specification & Electrical Specification
Electric standard IEC61009; GB 16917.0
Trip time Non-time delay; Minimal 10ms time delay
Rated voltage 230V; 50HZ          230V/400V
Rated surplus operating current 10; 30; 100; 300mA
Selection grade 3
Rated braking capacity 10kA
Rated current 6-63A
Tripping character B, C, D characteristic curve
Maximum connected fuse 100A gL(> 10kA)
Environment  capability According to the IEC 1008 standard
Case protection grade IP40 after installation
Electric life Not less than 4000 times of breaking and closing
Mechanical life Not less than 2000 times of breaking and closing
Mechanical Parameter
Installation mode Installation at the DIN guide rail of 35mm
Terminal block capacity Generatrix thickness 0.8-2mm

 

 

Normal working condition and installation condition:

 

1. The maximum ambient temperature should be -5°C≤T≤40°C,average temperature should be ≤35°C

 at 24h

 

2.The altitude of installation place should not exceed 2000m.

 

3. The relative humidity should not exceed 50% at 40°C, it permits higher relative humidity when at a higher temperature, the average maximum relative humidity should not exceed 90% at maximum humidity month, and this month′s average minimum temperature does not exceed +25°C, and should take consideration of the condensation on the product′s surface for temperature change.

 

4. Pollution grade: 2

 

5. Installation type: 1,2

 

6. The external magnetic field of installation place should not exceed 5 times of earth magnetic field.

 

7. The mini circuit breaker is installed by standard mounting rail.

 

8. The mini circuit breaker is upright installation, knob upwards is switch on position

 

9. The installation place should be without obviously impact and libration.

 

 

Tripping Curve:

 

3 Pole 10000A Earth Leakage Mini Circuit Breaker Overload Protection 0

Contact Details
Zhejiang KRIPAL Electric Co., Ltd.

Contact Person: Allen

Send your inquiry directly to us
Best Products
Other Products